1. Overview:

Gas relay (also known as gas relay) is a kind of protection device used in transformer. It is installed in the pipeline between oil conservator and oil tank of transformer. When oil is decomposed to produce gas or oil surge due to internal fault of transformer, the contact of gas relay will act and the specified control circuit will be connected, And timely send out signal alarm (light gas) or start the protection element to automatically cut off the transformer (heavy gas).

The light gas is mainly reflected in the operation or slight fault, the gas decomposed by oil rises into the gas relay, the air pressure makes the oil level fall, the open cup of the relay falls with the oil level, the light gas dry spring contact is connected to send a signal, when there is too much gas in the light gas, the gas can be discharged by the gas nozzle of the gas relay.

Heavy gas is mainly reflected in the transformer serious internal fault (especially the turn to turn short circuit and other faults that transformer protection can not act quickly). The strong gas pushes the oil flow to impact the baffle, and the magnet on the baffle attracts the dry spring contact of heavy gas, which makes the contact connect and trip.

Gas relay is divided into on load gas relay (oil pipe radius is generally 50mm or 80mm) and body gas relay (oil pipe radius is generally 80mm). There are different models of gas relay, such as float type, baffle type, open cup type, etc. For example, the signal circuit of qj-80 relay is connected to the open cup, and the trip circuit is connected to the lower baffle. The so-called gas protection signal action means that the signal circuit contact of the upper open cup in the relay is closed and the light plate light is on due to various reasons.

The company also supplies similar products of the above products: qj1-50 qj4-80 gas relay

2. Model parameters:

Purpose: qj-50 gas relay (hereinafter referred to as relay) is a protective device for oil immersed transformer with oil conservator and on load voltage regulating switch. The relay is installed in the connecting pipeline between transformer and on load tap changer oil tank and oil conservator

Technical parameters:

Oil flow speed range and factory setting value of trip contact action

model QJ4-80 QJ4-50 QJ4-25

Velocity range 0.7-1.5m/s 0.6-1.0m/s 1.0m/s

Factory setting 1.0m/s 0.8m/s 1.0m/s

1. Relay pipe diameter:

Qj4-25 type is ф 25, qj4-5o is ф 50, qj4-80 is ф eighty

2. Working temperature of relay: - 30 ℃ - + 95 ℃

3. Action gas capacity of signal contact: 250-300cm3

4. Rated capacity of contact: 220 V 0.3A, 110 V 0.6A (s 5x10 s)

5. Insulation strength: 2000V / NIM